N2XBY XLPE STA CABLE,CU/XLPE/STA/PVC

CU/XLPE/STA/PVC 600/1000V N2XBY XLPE Insulated Cable

N2XBY cable is suitable for AC 50Hz power and distribution lines with rated voltage of 600/1000V, which can be used   

· in fixed industrial power applications

· Underground tunnels

· in power and switching stations

· local energy distributions

· industrial plants

Using steel tape armouring offers great mechanical protection, making it rigid with a large radius installation indoors and outdoors.

 For any more information or advice please contact the office on 0086-13229065196(WhatsApp/WeChat)

Share:

Details

600/1000V,XLPE Insulated Cables, With steel tape armoured,PVC Sheath

0.6/1 KV CU/XPLE/STA/PVC cable plays a vital role in low-voltage power transmission and distribution, widely applied in building,industrial, and infrastructure settings to ensure the reliability and safety of power systems. This Power Cable with stranded compacted copper conductor is composed of copper conductor (CU), cross-linked polyethylene insulation (XPLE), steel tape armoring for mechanical protection and a polyvinyl chloride sheath (PVC). For fixed installation in interiors,outdoor installation,in soil,in water and concrete,if no posterior mechanical damage is to be expected.

Construction

N2XBY XLPE STA CABLE,CU/XLPE/STA/PVC

Description: N2XBY, XLPE Insulated Copper Power Cable   

Conductors: Class 1 or Class 2 of plain copper,or of Class 5 of plain copper in accordance with IEC 60228.

Insulation: Cross-linked polyethylene XLPE

Insulation Colour: Natural or as required

Filler:  Non-hygroscopic Material

Inner Sheath:  Polyvinyl Chloride PVC

Reinforcement: Steel Tape
Outer Sheath: Extruded Polyvinyl Chloride PVC&Polyethylene PE&LSZH
Colour of Sheath:  Black
Voltage Rating (Uo/U): 600/1000V   
Test Voltage: 3.5kV for 5 minutes

Physical Properties

Maximal operating conductor Temperature: up to 70℃(PVC insulation); up to 90(XLPE insulation)

Operating Temperature Range: -5℃(PVC or LSZH sheath); -20℃(PE sheath)

Short Circuit Temperature(5 seconds maximum duration): 140-160℃(PVC insulation);250℃(XLPE insulation)

Technical Data

0.6/1kV-2 core copper conductor XLPE insulated PVC sheathed power cable
No. of cores and nominal cross sectionThickness of Insulationsteel tape thicknessThickness of SheathApprox. overall DiameterApprox. weightMax. DC resistance of conductor(20℃)Current carrying capacity
(mm2)(mm)(mm)(mm)(mm)(kg/km)(Ω/km)In Air(A)In Ground(A)
2X2.50.7 0.2 1.8 12.4230 7.413346
2X40.7 0.2 1.8 13.4277 4.614359
2X60.7 0.2 1.8 14.4336 3.085575
2X100.7 0.2 1.8 16.0452 1.8376100
2X160.7 0.2 1.8 17.8609 1.1597130
2X250.9 0.2 1.8 20.8845 0.727130165
2X350.9 0.2 1.8 23.01065 0.524160200
2X501.0 0.2 1.8 26.01297 0.387195240
2X701.1 0.2 1.9 29.41775 0.268245290
2X951.1 0.2 2.1 32.82340 0.193305355
2X1201.2 0.5 2.2 37.93238 0.153355405
2X1501.4 0.5 2.3 41.73971 0.124405450
2X1851.6 0.5 2.4 45.74845 0.0991465510
0.6/1kV-3 core copper conductor XLPE insulated PVC sheathed power cable
No. of cores and nominal cross sectionThickness of Insulation steel tape thicknessThickness of SheathApprox. overall DiameterApprox. weightMax. DC resistance of conductor(20℃)Current carrying capacity
(mm2)(mm)(mm)(mm)(mm)(kg/km)(Ω/km)In Air(A)In Ground(A)
3X2.50.7 0.2 1.8 12.9265 7.412839
3X40.7 0.2 1.8 14.0328 4.613751
3X60.7 0.2 1.8 15.1410 3.084764
3X100.7 0.2 1.8 16.8560 1.836586
3X160.7 0.2 1.8 18.7775 1.1584110
3X250.9 0.2 1.8 22.01098 0.727110140
3X350.9 0.2 1.8 24.41410 0.524135170
3X501.0 0.2 1.8 27.61780 0.387170205
3X701.1 0.2 2.0 31.52475 0.268215250
3X951.1 0.5 2.1 36.83260 0.193265300
3X1201.2 0.5 2.2 40.54477 0.153310345
3X1501.4 0.5 2.3 44.65440 0.124350385
3X1851.6 0.5 2.4 49.16707 0.0991405435
3X2401.7 0.5 2.6 54.88533 0.0754480500
3X3001.8 0.5 2.7 60.010455 0.0601555565
0.6/1kV-4 core copper conductor XLPE insulated PVC sheathed power cable
No. of cores and nominal cross sectionThickness of Insulation steel tape thicknessThickness of SheathApprox. overall DiameterApprox. weightMax. DC resistance of conductor(20℃)Current carrying capacity
(mm2)(mm)(mm)(mm)(mm)(kg/km)(Ω/km)In Air(A)In Ground(A)
4X2.50.7 0.21.813.7308 7.412839
4X40.7 0.21.815.0388 4.613751
4X60.7 0.21.816.2488 3.084764
4X100.7 0.21.818.1681 1.836586
4X160.7 0.21.820.3960 1.1584110
4X250.9 0.21.823.91375 0.727110140
4X350.9 0.21.826.61779 0.524135170
4X501.0 0.21.930.42296 0.387170205
4X701.1 0.22.134.73175 0.268215250
4X951.1 0.52.340.44665 0.193265300
4X1201.2 0.52.444.55728 0.153310345
4X1501.4 0.52.649.76999 0.124350385
4X1851.6 0.52.754.58657 0.0991405435
4X2401.7 0.52.960.711000 0.0754480500
4X3001.8 0.53.166.413587 0.0601555565
0.6/1kV-5 core copper conductor XLPE insulated PVC sheathed power cable
No. of cores and nominal cross sectionThickness of Insulation steel tape thicknessThickness of SheathApprox. overall DiameterApprox. weightMax. DC resistance of conductor(20℃)Current carrying capacity
(mm2)(mm)(mm)(mm)(mm)(kg/km)(Ω/km)In Air(A)In Ground(A)
5X2.50.7 0.21.815.6350 7.412839
5X40.7 0.21.816.8447 4.613751
5X60.7 0.21.818.2569 3.084764
5X100.7 0.21.821.6805 1.836586
5X160.7 0.21.824.61150 1.1584110
5X250.9 0.21.829.01655 0.727110140
5X350.9 0.21.931.02166 0.524135170
5X501.0 0.22.135.72945 0.387170205
5X701.1 0.52.342.44453 0.268215250
5X951.1 0.52.447.25862 0.193265300
5X1201.2 0.52.651.87176 0.153310345
5X1501.4 0.52.757.68770 0.124350385
5X1851.6 0.52.963.810827 0.0991405435
5X2401.7 0.53.270.713770 0.0754480500
5X3001.8 0.53.478.016960 0.0601555565